DUSTLOK® 3-Ply Panel Media - Technical Data
DUSTLOK® Dual-Ply Polyester Media - Technical Data
More Specifications:
Filter Media: Polyester
Initial Resistance: 0.25” w.g. at 300 fpm
Flammability: UL 900 Classified
Performance: MERV 9 media
Dust Holding Capacity: 210 grams
Recommended Final Resistance: 1.0” w.g.
Maximum Operating Temperature: 200° F